HTT series P-type 15-400K UPS

HTT series P-type 15-400K UPS

Type : high frequency ups
Phase : 3 phase
Power Factor : 1
Input voltage : 380v/400v/450v
Input frequency : 50/60hz
INQUIRY DOWNLOAD PDF Format
Details
Features
Parameters

The HTT series P-type 15-400K UPS is a true online double-conversion, static, three-phase uninterruptible power supply system. Using IGBT power conversion technology of Vienna topology, ABM intelligent battery management system and other worlds. Advanced technology, combined with the world's mainstream trends of green, environmental protection, energy saving and the industry's advanced module technology, with excellent technical indicators, can effectively block the impact of abnormal power supply on the load, and provide reliable, pure and stable uninterrupted output power. 


Parameter

HTT- P series

Normal UPS

Input power factor

>0.99

>0.9

Whole unit efficiency

>94%

>90%

THDV

≤2%

≤5%

Output power factor

0.9

0.7~0.8

Overload capacity(125%load constant time

10mins

1min



Model

HTT-P 15K-60K

HTT-P 80K-200K

HTT-P 300K-400K

Capacity

15

20

30

40

50

60

80

100

120

160

200

300

400


Mains input


Input phase

3 phase 4 wires+ G

Input  rated voltage

380/400/415Vac

Input voltage range

190/330-276/478V-15%~20%) 100% load

116/201-276/478V-50%~20%) 50% load

Input frequency

50/60 Hz

Input frequency range

42-72Hz

Current harmonic

<2%linear load

Input power factor

>0.99

Battery


Battery nominal voltage

384Vdc (internal)/432Vdc (external) 

480Vdc

Battery quantity

32/36pcs/group(can set as 32-40pcs/groupEven number optional)

40pcs/group (can set as 36-44pcs/group, Even number optional)

Battery charging curve

Advanced ABM battery management (parameters can be customized)

output


Output voltage accuracy

±1%

Output nominal voltage

380 (default)/400/415 Vac 3phase 4 wires

Efficiency

≥94%

Output voltage harmonic distortion

Linear load <2%   

Non-linear load<5%

Rated output frequency

50 Hz (default) /60 Hz

output frequency range

±3Hz (default) (optional ±1Hz to ±4Hz)

Output frequency accuracy

±0.005Hz (single unit), ±0.07Hz (parallel unit)

Frequency response rate

3 Hz/s

Output power factor

0.9

Overload capacity

≤110 % 1hour;≤125 % 10mins; ≤150 % 1min; ≥150 % 150ms

Crest factor

3:1

Bypass


Bypass range

-15%~15%(can set as -10%~10%, -20%~20%)

ECO mode

standard

Parallel


Maximum number of parallels

4 Pcs

Parallel circulation

<5%

Environmental indicator


Working temperature

040℃

Storage temperature

-1555℃

Altitude

< 1000 meters

Humidity(storage and working)

5 %95 % No condensation

Noise

55dB

62dB

65dB

≤68dB

≤70 dB

≤73 dB

UPS size (W*D*H) mm

500*706*906

500*706*1230

500*706*1500

600*796*1876

600*806*1876

1200*820*1880

Net weight Kg

70

86

120

200

280

310

455

800

900


Total weight

100

120

160

260

350

378

523

900

1000